How is DC cable sizing and voltage drop calculated?
Easy PV returns the smallest cable cross-sectional area that achieves a voltage drop less than 1% of the voltage across the cable (or the largest cable if none do).
The voltage drop along a cable is the product of the current and resistance. The current is calculated in the inverter task and we calculate cable resistances from the IEC 60228/BS 6360 stranding chart.